HomeMy WebLinkAboutBuilding Board of Appeals 1990 Minutes r •,• !
OFFICIAL PROCEEDINGS •.rLLRK
of the U I: .--
'44 RUG 29 8M 9 26
BUILDING BOARD OF APPE
AUGUST 14, 1990
The regular meeting of the City of Lansing Building Board of Appeals
was held on Tuesday, August 14, 1990, in the Building Safety Division
Conference Room, 119 North Washington Square Annex, Lower Level ,
Lansing Michigan.
Chairman Richard Stuckman called the meeting to order at 2:02 p.m.
The following members were present and constituted a quorum:
Members Present:
Richard Stuckman, Chairman
Richard Jones , Vice Chairman
Frank Throop, Member
Randall Kamm, Member
Joe Wilcox, Member
Staff Present
Jack Nelson, Recording Secretary
Robert O'Brien, Fire Marshal
There was no modification to the agenda. On a motion by Mr. Jones,
supported by Mr. Throop, the minutes of the July 10, 1990, Board
meeting were approved.
OLD BUSINESS:
Appeal #90-009 - 221 N. Washington
This appeal was tabled from the July 10, 1990, meeting to afford
Michigan Bell sufficient time to gather additional technical informa-
tion for the Board. The appeal addresses the proposed remodeling
of the 6th floor of the Michigan Bell Telephone building for office
use. This remodeling has triggered High-Rise requirements contained
in Section 1807 of the U.B.C. Michigan Bell has taken exception to
the Department' s position and requests relief from the Board.
Those in attendance representing Michigan Bell were as follows:
Darell Loy, Assistant Manger, Building Planner - Michigan
Bell
George Reynolds, Manager, Service Continuity Team -
Michigan Bell
Al Goudreau, A. I .A. - Goudreau/Wakely Architects
Building Board of _,peals
Minutes
8/14/90
Page 2
Mr. Goudreau addressed the Board and presented a proposal which
requested a modification of the City of Lansing Uniform Building
Code to permit the acceptance of Appendix Chapter 1, Division 2 of
the 1985 Uniform Building Code, Life Safety Requirements for
Existing High-Rise Buildings" , in lieu of Section 1807 of the 1988
Uniform Building Code.
Mr. Goudreau stated that over a period of time the proposal , if
approved, will result in a facility that is fully compliant with
the Uniform Building Code requirements for existing high-rise build-
ings.
Second, the building will also be compliant with six of eight Subsec-
tions under 1807 of the 1988 Uniform Building Code which are as
follows:
(D) Smoke Detection Systems
(E) Alarm and Communication Systems
(F) Central Control Station
(H) Elevators
(I) Standby Power, Light and Emergency Systems
(J) Exits
Mr. Goudreau also stated that the existing building is currently
equipped with standby power which can provide power to smoke detection
systems, alarm and communication systems , elevators, essential power
and lighting to exit corridors and exit stair towers , thus , making
the building complaint with 1807 of the 1988 Uniform Building Code.
Mr. Goudreau also stated that application of existing high rise
requirements under the 1988 U.B.C. would be for the 6th Floor only
and would address fire safety concerns in a small portion of the
building. Michigan Bell ' s proposal would enhance fire safety in
the entire building.
Mr. Darell Loy addressed the Board and stated that Mr. George Reynolds
was attending the meeting in order to answer any technical questions
the Board may have on the ramifications of water from a fire suppres-
sion system contaminating the sensitive telephone equipment.
Mr. Loy also stated that his consultant has applied the existing
building requirements of Chapter 32 of the State Building Code to
this building. The analysis suggests that if the building had
achieved a sufficient point total not to require total fire suppres-
sion. Mr. Loy reiterated that Michigan Bell is aware that the
methodology is not a part of the U.B.C. , however, is submitted only
as a tool for fire safety evaluation.
Building Board of --peals
Minutes
8/14/90
Page 3
Chairman Stuckman requested input from Staff. Mr. O'Brien stated
that he felt comfortable with -the proposal .
Mr. Nelson stated that the proposal achieved more than the narrow
scope of triggering 1807 on one floor.
General discussion ensued. After discussion, Mr. Throop moved that
the proposal be accepted by the Board with the following conditions:
1. That the Building Board of Appeals retain jurisdic-
tion on this case.
2. The schedule of implementation as referenced under
Item #2 be revieweJ and approved by the Board.
Motion seconded by Mr. Jones.
The Chairman asked for discussion. Mr. Nelson requested the following
editorial changes in the document:
Item #2 - Change "adoption" to acceptance.
Item A - Change "1985" tc 1988.
Chairman Stuckman stated tha-: since Michigan Bell had not had an
opportunity to review the d- fferences between the 1985 and 1988
Uniform Building Code, "Life .,afety Requirements for Existing High-
Rise Buildings" , that they bE afforded additional time for review.
Mr. Goudreau stated that a review of the code would be performed
and a new proposal would be submitted which would incorporate the
requested changes.
Chairman Stuckman directed ! taff to coordinate the redraft with
Michigan Bell .
Chairman Stuckman asked for the Question. Motion carried unanimous-
ly.
The Building Board of Appeals does hereby resolve to accept the
following proposal in lieu of application of the 1988 Edition of
the U.B.C.
Request is hereby made to modify the City of Lansing Uniform Building
Code to permit the following:
(a) Acceptance of Appendix - Chapter 1, Division II of
the 1988 Uniform Building Code, "Life Safety Requirements
for Existing High-Rise Buildings" , in lieu of Section
1807 of the 1988 Uniform Building Code.
Building Board of ,ppeals
Minutes
8/14/90
Page 4
The entire building shall be made to conform with the following
requirements of Appendix - Chapter 1, Division II of the 1988 Uniform
Building Code, "Life Safety Requirements for Existing High-Rise
Buildings" within the following parameters:
1. The owner will complete within six months of accep-
tance of Appendix - Chapter 1, Division II , the
requirements of Subsection (27) Fire Drills.
2. The owner will submit within six months of accep-
tance of Appendix - Chapter 1, Division II, the
intended method(s) of bringing the entire building
into compliance with Subsection (2) Automatic
Sprinklers; (8) Shaft Enclosure Opening Protection;
12 Stair Shaft Ventilation; 16 Exit Corridor
Construction; 19 Exit Corridor Dead Ends.
3. The existing building is currently compliant with
Appendix - Chapter 1, Division 11, in the following
Subsections, (7) Vertical Shaft Enclosures; (10)
Automatic Elevator Recall System; 11 Unlocked
Stairway Doors; 15 Exit Stairways; (20) Interior
Finish; 21 Exit Stairway Illumination; (22) Exit
Corridor Illumination; 23 Exit Stairway Exit
Signs ; and 24 Exitway Exit Signs.
4. Within one year of adoption of Appendix - Chapter
1 , Division II, the owner shall bring the entire
building into compliance with the following Sub-
sections, (14) Posting of Elevators , (17) Exit
Corridor Openings , 18 Exit Corridor Door Closers,
and 25 Emergency Plan, and 26 Posting of
Emergency P an and Exit Plan.
5. Within two years of acceptance of Appendix - Chapter
1 , Division II the owner shall bring the entire
building into compliance with Subsection (3) Fire
Department communication_ System, and (6) Occupant
and Voice Notification System. In addition, this
system will be compliant with Section 1807 of the
1988 Uniform Building Code, relative to smoke detec-
tion, voice alarm system, public address system,
fire department communication system, and central
control station.
NOTE: The above scenario represents the modified version
which has been drafted by Michigan Bell and approved by
the Building Safety Division. Note that the following
Sections have been deleted from the Appendix - Chapter
pages 819-823 of the U.B.C. 1988.
Building Board of eals
Minutes
8/14/90
Page 5
Item 7#5 - Manual Fire Alarm System
Item #12 - Elevator Shaft Ventilation
Item #9 - Manual Shut-off of HVAC Systems
In support of this decision The Board makes the following findings
of fact:
1. The Appendix Chapter(s) for existing high-rise buildings have
not been adopted by the City of Lansing. The use of this
document lends a reasonable approach which addresses existing
buildings.
NEW BUSINESS:
Appeal #90-015 _ 2800 N. Grand River
An application for appeal has been filed by Mr. Todd Kessler of
D.L. Kessler Construction Company on behalf of Mr. Dan Gorman,
Owner.
The appeal seeks relief from Section 3305(g) of the Lansing Uniform
Building Code, as amended. The applicant is currently constructing
a 11,999 sq. ft. retail grocery store at 2800 N. Grand River Avenue.
The minimum Construction Type of the building is V-N Combustible,
the actual Construction Type is II-N. The Use Group classification
is Group B, Division 2, Retail Sales. The entire building is
protected by an automatic fire suppression system.
Those in attendance representing Mr. Dan Gorman were Darell Kessler,
Kessler Construction, and Paul Barbour, Architect.
Mr. Paul Barbour addressed the Board. Mr. Barbour described the
building and stated that the building is fully sprinkled and is of
non-combustible construction. Mr. Barbour represented that if the
building were constructed in Delta Township or under State jurisdic-
tion, the rated corridor for the second exit would not be necessary.
It was also stated that modifications to the building were necessary
in order to accommodate changes in equipment.
Mr. Jones stated that he did not feel that the situation was particu-
larly hazardous since the corridor was only 21 ' in length. Further-
more, the building is sprinkled and of non-combustible construction.
It was also stated that if the building was classified as an office,
fire suppression coupled with smoke detection would meet the code.
Mr. Wilcox stated that the record showed that the Architect was
notified of the deficiency in the plan review. The plans were
amended but not followed.
Building Board of eals
Minutes
8/14/90
Page 6
After general discussion Mr. Jones moved that the variance be granted.
The motion died for lack of support.
Mr. Wilcox moved that the motion be denied, supported by Mr. Kamm.
Chairman Stuckman asked for discussion on the motion.
Mr. Jones requested alternatives under which the variance could be
granted. Mr. Wilcox stated that a proposal which afforded the same
degree of safety should be submitted by the applicant. He also
stated that he would be willing to review such a proposal .
Chairman Stuckman asked for the Question.
Motion carried, 3 yeas (Kamm, Wilcox, and Throop) ; 1 nay, (Jones) .
Appeal denied.
Appeal #90-016 - 808 Barnes Avenue
An application for appeal has been filed by Mr. Joseph O'Leary on
behalf of Rev. Kenneth J. Povish, Bishop of Lansing.
The appeal seeks relief from Table 5-A of the Lansing Uniform Building
Code, 1988 Edition, as amended. The building was previously utilized
as a convent. Table 5-A states that the fire resistance of exterior
walls is one hour when less than 5 ' to the property line and
openings are not permitted less than 5' from the line. The building
is being converted to offices. Table 5-A requires that the wall be
one-hour construction when less than 20' to the property line and
all openings in the exterior wall shall be protected when less than
10' to property line.
Second, the applicant is requesting authority to use the second
floor for offices which only has one means of egress.
Mr. Joe O'Leary addressed the Board and stated that the Church is
requesting the Board to waive the requirement that the windows be
protected and that a second exit be provided. The very limited use
of this building will not create as much fire hazard as the previous
use since there will be no cooking. Second, only three people will
utilize the second floor and it will be limited to office use. Mr.
O'Leary also stated that the next door neighbor, the Aboods, have
no objection to the variance.
After general discussion Mr. Wilcox moved that both variances be
granted with the condition that the variance is valid for only as
long as the Church has ownership and the use is not intensified.
Motion supported by Mr. Jones.
Building Board of peals
Minutes
8/14/90
Page 7
Chairman Stuckman asked for discussion on the motion.
Mr. Nelson requested that the approval be conditioned upon posting
the second floor for a maximum occupant load of 9.
Mr. O'Brien requested that the approveal be conditioned upon the
installation of monitored smoke detection which serves the entire
building.
Chairman Stuckman asked if Mr. Wilcox would amend his motion to
incorporate these two points , and also asked if Mr. Jones would
support the amendment?
Mr. Wilcox moved to mend his motion, Mr. Jones supported the motion.
Voting on the amendment, motion carried. Voting on main motion,
motion carried. Variance granted.
In support of this motion the board makes the following findings of
fact:
1. The proposed use, though a change in use group, is less intense.
2. The second floor will be limited to an occupant load of nine
persons which is allowed for one exit by Chapter 33 of the
U.B.C.
3. The smoke detection system will provide an early warning system
and will equate with code compliance.
Appeal #90-017 - 1401 E. Miller Road
An application for appeal has been filed by Mr. Barry Wood, A. I .A.
of Stein, Hinkle, Dawe, Wood and Johnson, on behalf of Continental
Cablevision of Michigan.
The appeal , if granted, would aulthorize the use of an automatic
egress control device on one of the exit doors in the lobby of the
proposed building. Section 3304(e) of the U.B.C. authorizes the
use of special egress control devices on exit doors in offices only
when the building is protected throughout by an approved automatic
sprinkler system and an approved automatic smoke detection system.
The device shall also conform to the following excerpt from the
Uniform Building Code, Chapter 3304(e) .
Mr. James Aubuchon, A. I .A. , represented the building's owner. Mr.
Aubuchon stated that the egress control device is located on the
second exit of the front office lobby. The calculated occupant
Building Board of eals
Minutes
8/14/90
Page 8
load exceeds 50, however, the anticipated number of people is only
15-20. An automatic smoke detection system would be provided in
the front office/lobby to deactivate the egress control system. A
second means of egress out the front is not possible due to the
topography of the site.
Mr. Stuckman asked for comments from Staff. Mr. O'Brien and Mr.
Nelson voiced concern over locking one of the required exits.
Mr. Jones moved that the variance be denied stating that there are
otherways to enforce security. Security risks do not out-weigh
fire safety concerns.
Motion supported by Mr. Throop. Motion carried unanimously.
Appeal #90-018 - 2140 Mint Road
An application for appeal has been filed by Mr. Carl Schmidt on
behalf of AIRCO Gases.
The variance, if granted, will authorize the construction of a
cylinder-filling building which does not comply with the following
requirements of the U.F.C. 1988 Edition and U.F.C. 1985 Edition.
"Explosion Venting of Structure"
1. Section 910 U.B.C. 1988, and Section 8.301Q U.F.C. 1985
2. Emergency Lighting 3313 U.B.C.
3. Exiting 3320 U.B.C. 1988
Those in attendance representing AIRCO were Carl Schmidt, Regional
Production Engineer, AIRCO Gases , and Don Hartwick of Rother and
Hartick. Mr. Schmidt addressed the Board and stated that Airco
Gases is a nationwide manufacturer and distributor of compressed
gas products and has served the Lansing area for over 50 years.
Their current location is at 2140 Mint Road in Lansing, which has
been safely operated since moving there in 1975. Among the gases
distributed from this location is hydrogen. Their largest customers
for this product include the Board of Water and Light, Michigan
State University, and Federal Mogul , who relies on hydrogen to
supply the automotive industry with specialty products. Hydrogen
is currently shipped to the site from other AIRCO locations where
the cylinders are filled.
Variance ttl : Explosion Venting
As a supplement to the Uniform Building Code, it is desired to
design the building using the recommendations of the N.F.P.A. through
the following codes:
Building Board of gals
Minutes
8/14/90
Page 9
NFPA 50A: Standard for Gaseous Hydrogen Systems at
Consumer Sites.
NFPA 68: Guide for Venting of Deflagrations.
Explosion venting is a common method of relieving the overpressures
that develop within an enclosure when a combustible mixture of gas
or dust is inadvertently burned. During this burning, the products
of combustion expand rapidly and can cause significant damage to
weak structural components of the enclosure. To prevent the
catastrophic failure of the structure under these conditions, one
or more elements of the enclosure are specifically designed to fail
at low overpressures. The openings that result are sized to relieve
the expanding gases.
NFPA 50A Paragraph 4.2.3. addresses the topic of explosion venting
for separate buildings that house gaseous hydrogen systems and it
gives specific requirements for systems with less than 15,000 cubic
feet of hydrogen. For buildings that contain over this amount, it
refers to NFPA 68. The proposed building will house more than
15,000 cubic feet of hydrogen in compressed gas cylinders and process
piping, therefore, NFPA 68 was consulted for guidance.
The following definitions are taken from NFPA 68:
Deflagration: Propagation of a combustion zone at a velocity that
is ess than the speed of sound in the unreacted medium.
Detonation: Propagation of a combustion zone at a velocity that is
greater than the speed of sound in the unreacted medium.
Explosion: The bursting or rupture of an enclosure or a container
due to the development of internal pressure from a deflagration.
NFPA 68, Chapter 4, is entitled "Venting of Deflagrations in Low-
Strength Enclosures" . This chapter addresses the explosion venting
requirements for rooms and buildings in which a deflagration may be
possible due to the presence of combustible mixtures of flammable
gas or dusts. Within this chapter, an equation is presented which
allows the user to calculate the recommended vent area given the
following information:
Internal surface area of the enclosure
Vent release pressure
Fuel characteristic for the combustible product
The first of these is based on the building size, the second can be
found in the Uniform Building Code Section 910 and the third is
found in Table 4-3 of NFPA 68.
Building Board of r eals
Minutes
8/14/90
Page 10
NFPA 68 fails to provide a fuel characteristic for hydrogen gas but
specifically addresses it in paragraph 4-3.3.2. In summary, hydrogen
is a fast-burning gas and very high rates of combustion as well as
detonations have been observed in actual practice. It states that
no recommendations can presently be given for fast-burning gases
and that even if a detonation does not occur, it may not be possible
to vent a deflagration involving hydrogen.
The Uniform Building Code, Section 910, provides guidance with regard
to explosion venting. It gives specific requirements for deflagra-
tions and for very small detonations (less than 2.0 grams TNT equiva-
lent) . For situations where detonations are considered likely, it
calls for the use of protective devices or systems and implies that
they would be in lieu of explosion venting. The Code, however,
does not provide specific information on the types of devices or
system that should be implemented.
It is proposed that the explosion venting requirement be waived due
to the tendency of combustible hydrogen gas mixtures to detonate
rather than deflagrate. In addition, it is proposed that protective
devices serve to prevent detonation from occurring instead of
providing after-the-fact protection of the surrounding exposures.
The following are the features proposed to prevent the accumulation
of combustible mixtures within the building.
1. Continuous, non-recirculating ventilation
2. A multipoint combustible gas monitoring system
3. Dilution ventilation
4. Process termination actions
5. Audible alarms
It is desired to upgrade the site to include hydrogen gas cylinder
filling, a well established and safe practice that AIRCO has followed
for years without incident. In the process of developing a suitable
installation, applicable standards were reviewed with both Building
and Fire Department Officials. They have recommended that further
review be conducted through the Board of Appeals in order to define
the requirements for the cylinder filling building.
Liquified hydrogen is to be stored on-site in an approved vessel ,
pumped and expanded into hydrogen gas. The gaseous hydrogen will
be pressurized into Department of Transporation approved containers
for shipment off-site. The process of filling cylinders maintains
the gas within the piping and the cylinders at all times. Releases
of the gas is considered an abnormal condition. The issue at hand
is the design features for a separate building, dedicated for filling
hydrogen gas cylinders .
Building Board of P^neals
Minutes
8/14/90
Page 11
Mr. Schmidt then explained the second variance and submitted the
following information:
Variance #2: Exit Illumination
Uniform Building Code Section 3313 specifies that exit illumination
is required for our proposed building. This implies that special
illumination is required 'at the exit as a supplement to the normal
illumination provided. It is requested that supplemental lighting
fixtures not be required at the exit because the normal lighting
will provide the 1 foot-candle intensity at floor level .
After discussion it was the consensus of the Board that exit illumina-
tion could be provided from the on-premise wiring systems. The
occupant load of the structure did not require exit signage. Based
upon this discussion, the applicant withdrew this portion of the
variance.
Mr. Schmidt explained the third variance:
Variance #3: Exits in Group H Occupancies
Uniform Building Code Section 3320 addresses the number of exits
required for Group H Occupancies. Our proposed building will be
classified Group H, Division 2 because of the flammable gas. The
Code indicates that buildings in excess of 200 square feet be serviced
by at least two exits. It is understood that the reason for
requiring multiple exits in any enclosure is to provide the occupants
with an alternative means of egress in the event of a fire hazard
blocking their path to the primary exit. It is requested that only
one exit be required for the proposed building because the structure
will be non-flammable construction and the equipment and hardware
within the building will be metal .
After discussion, Mr. Jones moved that Variance #1 and #3 be approved
contingent upon compliance with the following:
1 . The building shall have a continuous , non-recirculating ventila-
tion system.
2. A Multi-point combustible gas monitoring system shall be
installed.
3. Dilution ventilation shall be provided.
4. Process termination actions shall be instituted.
5. Audible alarms shall be provided.
Motion supported by Mr. Throop. Motion carried.
Building Board of "repeals
Minutes
8/14/90
Page 12
In support of this decision, the Board makes the following findings
of fact:
I . Explosion venting will not be feasible in this building if a
detonation occurs. It is more prudent to provide mechanisms
for detection and prevention.
2. The conditions required by the Board will ensure that the
operation complies with the intent and purpose of the code.
3. The Report which was submitted by Mr. Schmidt entitled "Report.
To Supplement Request For Variance" shall be part of the record
and is hereby referenced as Findings of Fact.
There being no other business before the Board and no public comment,
Mr. Kamm moved to adjourn the meeting; supported by Mr. Throop.
Meeting adjourned at 4:57 p.m.
Respectfully Submitted,
ark Nelson
ry
JAN/mmr
Minutes Approved On
ANOZING
R K
OFFICIAL PROCEEDINGS
of the
BUILDING BOARD OF APPEALS '90 RUG P� 5 01
JULY 10, 1990
The regular meeting of the City of Lansing, Building Board of Appeals ,
was held on Tuesday, July 10, 1990, in the Building Safety Division
Conference Room, 119 N. Washington Square Annex, Lower Level ,
Lansing, Michigan.
Chairman Richard Stuckman called the meeting to order at 1:35 p.m.
The following members were present and constituted a quorum:
Members Present
Richard Stuckman, Chairman
Richard Jones, Vice Chairman
Frank Throop, Member
Randall Kamm, Member
Joe Wilcox, Member
Staff Present
Jack Nelson, Secretary
Robert O'Brien, Fire Marshal
Ralph Goff, Chief Mechanical Inspector
James Kzeski , Director of Building Safety
There was no modification to the agenda. On a motion by Mr. Jones,
supported by Mr. Throop, the minutes of May 8, 1990, were approved
as printed.
OLD BUSINESS: None
NEW BUSINESS:
Board Review - Cost Allocation Study
The City of Lansing has retained D.M.G. Public Sector Consultants
to perform a study of the City' s fee structure in order to determine
if the current fee structure covers program costs.
William Maxwell , Manager of D.M.G. Public Sector Consultants,
presented the cost allocation study to the Board and apprised them
of the proposed fee increases. The purpose of the presentation was
to afford an opportunity to the various city boards to submit comments
and recommendations to the Mayor prior to forwarding the study to
City Council for approval .
Building Board c ippeals
Minutes
July 10, 1990
Page 2
After hearing the presentation, the Board Members made the following
comments.
1. At issue is the question - To what degree does general taxation
subsidize programs?
After review of the cost allocation study it would appear that
100% cost recovery is being proposed. It is the general con-
census of the Board that the proposed increases are excessive
and the Board supports the Departments fee increase proposal
rather than that of the Consultant.
2. The Appeals Board acts as a pressure relief valve for Building
Code enforcement. The fee should not be the basis for detering
the filing of an appeal . The Board would support a dual fee
system which requires a minimal fee for appeals which pertain
to single-family residences and a separate fee for other pro-
jects.
3. Fees should be somewhat consistent with those charged in adjoin-
ing municipalities. This would promote development with the
City.
4. Plan review functions of the Planning, Traffic, Fire Prevention,
and Public Service Departments should be part of the Plan
Review Fee not the Building Permit Fee.
Appeal #90-008 - Network Technologies Corp. , 431 S. Capitol
An application for appeal has been filed by Mr. Fredric McLaughlin,
Architect, on behalf of the Building Owner, Mr. Stanely Kasuda.
The Applicant seeks relief from Section 3303(a) of the U.B.C. 1988
Edition which states that the second story shall be provided with
not less than two exits when the occupant load for the story is 10
or less.
Mr. McLaughlin explained the request to the Board and stated that
the second floor has approximately 780 square feet of area. However,
the east and west second floor is isolated from each other by a
common wall . An addition of 480 square feet will be added to the
west portion of the second floor which is currently 480 square feet
in area, for a total area of 960 square feet. The east portion of
the second floor is 300 square feet and will not be altered. The
total square footage of the two tenant spaces on the second floor
will be 1,260 square feet. The calculated occupant load for the
second floor is 13 persons. Currently, two exits are provided for
the story, however, the tenant spaces are divided by a wall which
precludes the use of the second exit by either tenant.
Building Board of .,ppeals
Minutes
July 10, 1990
Page 3
Chairman Stuckman asked for staff comments. Mr. O'Brien recommended
that smoke detection be installed in the Building.
Mr. Wilcox moved to authorize the variance subject to the following
conditions:
1. Smoke detection shall be installed in the building.
2. A rated access panel would be authorized in the wall . The
panel is not to have any hardware other than a key lock.
3. The existing lath and plaster wall will be accepted as a one-hour
separation wall .
The motion was supported by Mr. Throop, and passed unanimously.
In support of this decision, the Board made the following findings
of fact:
1. Each individual tenant space has a calculated occupant load of
less than 10 persons and is services by an independent exit.
2. The smoke detection system will afford an early warning system
for the building tenants in case of fire.
3. The Board feels that the intent of Section 3303(a) has not
been compromised.
Appeal #90-009 - Michigan Bell Telephone Co. , 221 N. Washington Sq.
An application for appeal has been filed by Mr. Darell Loy on
behalf of Michigan Bell Telephone Company.
Michigan Bell Telephone Company has apprised the Department that
they propose to remodel the 6th floor of the Michigan Bell building
for office use. In response to this information, the Building
Safety and Fire Protection Bureau has notified Michigan Bell that
alteration to the 6th floor will trigger compliance with the 1807
High-rise requirements. The Building Safety Divisions ' position is
based upon Section 104 of the Uniform Building Code which states
that areas altered shall comply with current Building Code require-
ments. Michigan Bell has taken exception to the requirement and
has requested a variance from the Building Code.
Mr. Darell Loy addressed the Board and stated that in lieu of
compliance with Section 1807 of the U.B.C. 1988 Edition, Michigan
Bell seeks authority to utilize Appendix 1-B, Part 2.2(a) of the
Uniform Building Code 1985 Edition (see attachment #1 dated June 5,
1990) .
Mr. Loy stated that the Bell building is equipped with a smoke
Building Board o, .,ppeals
Minutes
July 10, 1990
Page 4
detection system. Second, the building is concrete which reduces
the possibility of a fire. Third, the building is occupied 24
hours a day, so any fire would be detected immediately. Mr. Loy
also stated that Michigan Bell does not want the possibility of
water damage to the telephone equipment which would be a possibility
with the sprinkler system.
Mr. O'Brien, Fire Marshal , stated if a fire did occur the Fire
Department would utilize water to extinguish the fire, and that
less water would be expended from the sprinkler system since the
fire would have been contained or completely extinguished with the
sprinkler system.
After hearing the testimony, Mr. Jones moved to table the request
until the August 10, 1990, meeting in order for the applicant to
submit documentation which would support the appeal . Motion
supported by Mr. Throop. Motion carried unanimously.
Appeal #90-010 - Wal-Mart Properties, Inc. , 340 E. Edgewood
An application for appeal has been filed by M. Bradley Gaskin on
behalf of Wal-Mart Properties.
The appeal seeks relief from Section 1716.5 of the U.B.C. which
states that two exits shall be provided from a mezzanine when two
exits are required by Table 33-A.
Mr. Richard Misanhimer, Construction Manager, stated that the 1,420
sq. ft. mezzanine was originally constructed for storage, therefore,
it was not constructed with two exits. They are proposing to use
the mezzanine for an employee breakroom and tele-marketing. They
would limit the occupant load of the area to under 50 persons which
would only require one exit.
Mr. Stuckman asked for staff comments. Mr. Nelson recommended that
the mezzanine be divided by a wall in order to restrict the use of
the area.
The representative from Wal-Mart stated that they would have no
objection to the condition of a wall .
Mr. Jones moved that the variance request be granted, motion supported
by Mr. Wilcox. Mr. Throop moved to amend the original motion to
require that a partition be constructed between the office and
breakroom. The amended motion was supported by Mr. Kamm. Motion
carried.
The members then voted on the main motion which passed unanimously.
Building Board of Nppeals
Minutes
July 10, 1990
Page 5
In support of this decision the Board makes the following findings
of fact.
1. The occupant load of the mezzanine will be restricted to 50
persons.
2. The mezzanine will be subdivided in order to limit the occupant
load in the lunch room.
Appeal #90-011 - O'Leary Paint, 415 Baker
An application for appeal has been filed by Mr. David O'Leary on
behalf of O'Leary Paint Company.
The applicant seeks relief from Section 905(b) of the Uniform Building
Code and Sectin 79.804 of the 1985 U.F.C.
The variance request, if granted, would authorize the Paint Mix
Room to have four air changes per hour rather than six air changes
which are required by the 1988 U.B.C. , and the 1985 U.F.C. .
Chairman Stuckman notified the Board that he would abstain from
voting due to a conflict of interest. Mr. Stuckman stated that his
firm designed the facility.
Elgin Clark of Clark, Trombley, Randers, addressed the Board and
stated that less than 10% of the volume of paint which is mixed is
flammable. Also, each. mixing vat has a mechanical exhaust on it.
Mr. O'Leary stated that oil based paints will soon be outlawed and
the mix operation will be 100% latex. The plant only produces four
batches of oil based paint per month for a total of 2,000 gallons .
Chairman Stuckman asked staff for comments. The staff had no objec-
tion. Mr. Ralph Goff, Chief Mechanical Inspector, stated that in
his opinion the exhaust system on the vat coupled with the Mechanical
system for the room is sufficient to evacuate the mix room. Mr.
Nelson stated that initial review of the project was under the 1985
Edition of the U.B.C. which only required four air changes.
Mr. Kamm moved that the appeal be granted subject to the receipt of
a report from the engineering firm that the existing mechanical
system will change the air every 15 minutes. This was supported by
Mr. Wilcox. Motion carried.
In support of this decision, the Board made the following findings
of fact:
Building Board c ppeals
Minutes
July 10, 1990
Page 6
1. A very low volume of oil based paint will be mixed in the
facility and it appears that the amounts of oil based paints
mixed in the future will be negligible.
2. The Engineer, Mr. Elgin Clark, will certify that the mechanical
system will produce four changes of air per hour in accordance
with the provisions of the 1985 U.B.C.
Appeal #90-012 - Robert Hill , 5939 Rolfe
An application for appeal has been filed by Mr. Robert Hill , licensed
residential contractor, on behalf of the homeowner, Mr. Jon Hill .
The applicant seeks relief from Table 32.B(1) of the U.B.C. 1988
Edition which requires that Type 15# roll felt be applied to the
roof prior to shingle installation.
Mr. Hill addressed the board and stated that a mistake was made in
not applying the felt. Mr. Hill stated that the shingle supplier
had informed him that the felt was not required. Mr. Hill further
stated that this was the first time that he had worked in Lansing
and was not aware of the requirement.
Mr. Wilcox stated that as a licensed contractor Mr. Hill should
have known that both National building codes require felt.
After discussion, Mr. Jones moved, supported by Mr. Kamm, that the
appeal be granted. Motion carried with Mr. Wilcox voting nay on
the motion.
In support of this decision, the Board make the following findings
of fact:
1. The owner shall submit a letter which attests to acknowledgement
of the code violation.
2. The felt, although necessary to prevent roof leaks, will not
affect the health and safety of the occupants.
Appeal #90-13 - Marketing Resource Group, Inc. , 225 S. Washington
Sq.
An application for appeal has been filed by Mr. Thomas Shield's
tenant. The applicant seeks relief from Section 1703 and 3802 of
the U.B.C. 1988 Edition and Table 9-4 of the Lansing Uniform Plumbing
Code.
The variance, if authorized, would delete the necessity of a urinal
in the mens toilet room, a one-hour separation between the basement
and first floor, and a fire suppression system in< the basement.
Building Board kppeals
Minutes
July 10, 1990
Page 7
Mr. Shields stated that he is the owner of Marketing Resource Group,
a small marketing and public relations firm. He stated that he was
notified by the City that Building Code regulations would add an
additional 15,000 cost to the project. Mr. Shields submitted the
following arguments in support of his appeal .
"Item 1 - Fire Code requiring basements over 1 ,500 square
feet to have drywalled ceilings , sprinkler system and
fire door. "
1. "While we plan on installing a fire door, the base-
ment in question is just 1,555 sq. ft. - or 55 sq.
ft. over the code's limit. "
2. "The basement will not be used as a work area and
the following costs to install the drywall ceiling
and sprinklers could jeopardize the entire project. "
"The cost estimates are:
Drywall Ceiling $3-4,000
Sprinkler System $2-2,500
(Could possibly require a new 2" I .D. water main
from the Baord of Water and Light)
New Water Main $2-4,000
Remove and reinstall $1-2,500
Light fixtures, removal and disposal
of old plumbing
Approximately Total Cost $10,000
3. "The entire building is very well constructed and
already equipped with fire/security sensors through-
out the building. "
4. "As my business continues to grow, our long-term
plan would be to completely re-renovate the basement
into office space which would include the addition
of a new stairway in the middle of the floor.
This expansion and renovation would cause us to
completely tear down and rebuild the entire ceiling
and sprinkler system at a later date. "
"Item 2 - Barrier Free design requiring an additional
restroom to accommodate one urinal . "
1. "The building already has two restrooms , one is
barrier-free and is located on the first floor and
the other is located on the second floor. "
Building Board of appeals
Minutes
July 10, 1990
Page 8
2. "The logical location of a required additional rest-
room is next to the existing barrier-free restroom.
The additional space that this restroom requires
would eliminate much needed office space to meet
the demands of expansion. "
3. "Because of the location of the restroom, which is
located on a concrete floor (no basement or crawl
space) , the additional cost could be as high as
$3-5,000. "
4. "We currently have only 8 full-time employees and
are planning to expand to 13 or 14 when we move
into our new space. We feel that the two existing
restrooms are more than adequate, and the building
of an additional urinal is not needed. "
After discussion, Mr. Jones moved, and supported by Mr. Wilcox, to
grant the appeal provided a hardwired smoke detection system in the
building. Motion carried.
In support of this decision, the Board made the following findings
of fact:
1. The basement only exceeds the trigger for fire suppression by
55 sq. ft.
2. The basement ceiling contains plumbing and mechanical which
will cause difficulty in installation of a drywall ceiling.
It is felt that a smoke detection system will equate with the
drywall ceiling.
3. The actual occupant load of the building is 14 persons. The
Plumbing Code authorizes one uni-sex toilet room if the occupant
load does not exceed 15 persons.
Appeal #90-014 - HIMONT Advanced Materials , 2835 Alliance
An application for appeal has been filed by Mr. James Brown on
behalf of HIMONT Advanced Materials. The appeal seeks relief from
Chapter 52 of the U.B.C. 1988 Edition which limits the coverage of
CCI plastics to a maximum aggregate area of 33% of the floor area
of the space sheltered. Second, Major Industries Guardian Roof
Panel has not been approved via an ICBO Research Report.
Mr. Brown addressed the Board and stated that the roof system meets
Class A roofing test requirements as evidenced by the test report
conducted by Warnock Hersey International . Second, the building is
Building Board o ppeals
Minutes
July 10, 1990
Page 9
protected by an automatic fire protection system, and has a smoke
detection system. Mr. Brown also stated that the building exceeds
minimum requirements for number of exits and exit widths.
Chairman Stuckman asked for staff recommendations.
Mr. Nelson stated that the Department had no ojbection to the variance
if a dedicated fire suppression system was installed in the corridor
which was directed toward the roof panels. Also, a smoke detection
system is recommended in the corridor.
Mr. Brown stated that plans have been amended to include smoke
detection and fire suppression in the corridor.
Mr. Throop moved to grant the appeal . The motion was supported by
Mr. Jones. Motion carried.
In support of this decision, the Board makes the following findings
of fact:
1. The purpose of Chapter 52 is to limit the amount of combustibles
in a noncombustible building. In this case the roof will be
protected by a sprinkler system. A smoke detection system
will also be provided to give the occupants advanced warning
of a fire.
2. The roofing system meets Class A roofing requirements.
3. The building exceeds minimum code requirements in the following
areas:
Automatic Fire Suppression
Smoke Detectors
Number of Exits
Exit Widths
There being no other business before the Board and no public comment,
Mr. Kamm moved to adjourn the meeting; supported by Mr. Jones.
Motion carried unanimously. Meeting adjourned at 5:22 p.m.
Respectfully submitted,
Ja k A. Nelson
Se retary
Minutes Approved On:
OFFICIAL PROCEEDINGS
of the
BUILDING BOARD OF APPEALS
May 9, 1989
The regular meeting of the City of Lansing, Building Board of Appeals
was held on Tuesday, May 9, 1989, at 2:00 p.m. in the Building
Safety Division, 119 N. Washington Square Annex, Lower Level , Lansing
Michigan.
The meeting was called to order by Chairman Richard Stuckman at
3:00 p.m. with the roll call showing the following members present:
Members Present:
Richard Stuckman, Chairman
Frank Throop, Member
Randall Kamm, Member
ca
0
Members Absent:
rn
Richard Jones C
Staff Present: cn
rn
cn
Jack Nelson, Chief Plan Review Analyst
Robert O'Brien, Fire Marshal c:
On a motion by Mr. Throop, supported by Mr. Kamm, the minutes o
the January 17, 1989, special meeting were approved as printed.
OLD BUSINESS: None
NEW BUSINESS:
Appeal #89-003: Chirstman Company
An application for appeal was filed by Mr. Larry Macklin of the
Christman Company, 221 South Grand Avenue, Lansing, Michigan. The
appeal request was made to construct an 8' high fence conforming to
Section 4407(c) of the Uniform Building Code, 1985 Edition as a
means of pedestrian protection. The fence would be constructed
from the Northwest corner of the Black and Tan Bar, then East 88' ,
a distance of 6' from the bar. The fence would create an exitway
to Grand Avenue for the required exit from the bar.
Section 4407(a) of the Lansing Uniform Building Code requires a
fence and canopy since the subject area is within the sphere of
influence of the proposed grand tower.
Building Board of Appeals
Minutes
May 9, 1989
Page 2
Mr. Macklin presented his case stating that the operating hours of
the bar are 10:00 a.m. - 2:00 a .m. from the small bar located in
the front of the building, and 9:00 p.m. to 2:00 a.m. for the large
assembly area located in the rear of the bar. Mr. Macklin stated
that the occupants who would exit through the two North exits would
do so primarily during periods when no construction is in progress,
thus posing no danger of falling objects to pedestrians.
Further discussion on the topic substantiated that the northwest
exit door which opened on to the unprotected area was. a required
exit for the smaller front bar which had a calculated occupant load
of 92.
After continued discussion, Mr. Kamm moved that a variance be granted
from Section 4407(c) of the Lansing Uniform Building Code. The
variance will allow the use of 8' high opaque fence for use as
pedestrian protection along the North side of the building except
the Northwest exit shall be protected from the exit discharge to
Grand Avenue a sufficient distance to discharge occupants outside
of the sphere of influence. Motion seconded by Mr. Throop. Motion
carried unanimously.
In support of this variance the Board makes the following findings
of fact:
The entire length of the exit need not have a canopy
since the second exit (the Northeast) exit will only be
utilized during non-working hours.
This variance is predicated upon compliance with the following condi-
tions:
1. The construction of the pedestrian protection shall
comply with Chapter 44 of the Uniform Building
Code.
2. The enclosed portion of the pedestrian protection
shall be lighted.
3. Should the hours of operation of the Black and Tan
change such that the Northeast exit is utilized
during construction hours, a protective canopy shall
be constructed immediately.
4. The applicant shall submit written confirmation of
the hours of operation of the Black and Tan.
Building Board of Appeals
Minutes
May 9, 1989
Page 3
Appeal #89-004
An application for appeal was filed by Daniel R. Johnson of Hobbs
and Black Associates, Inc. , 100 N. State Street, Ann Arbor, Michigan.
The appeal was filed on behalf of Gentilozzi Real Estate. The
nature of the request concerned how the separation between the
exterior wall of the proposed Grand Tower and the property line
would be measured. Section 1803(b) of the Building Code requires
that the separation distance be measured from the exterior wall of
a building to the adjacent properlty line or center line of a
public way. The Grand Tower is apparently being constructed on a
parcel of property which was purchased from the City of Lansing and
has an irrevocable life-time lease for public access through the
property. Consequently, a question has risen as to whether the
distance for protection of openings on the North and South wall
should be measured to the property line, or the center of the
easement.
After considerable discussion, Mr. Throop moved that action on the
case be tabled until the next Board meeting in order to provide
time for the consummation of the written agreements between the
concerned parties. Upon completion of the following items the
appeal will be granted.
Second, that the Board of Appeals recommend that language be drafted
as a part of the agreement between the parties which would define
the public access easement as not adversely effecting the construc-
tion of the Grand Tower Building; that is to say for purposes of
construction the City would not treat the easement as a public way.
Third, that Gentilozzi Real Estate grant an easement to the Black
and Tan Restaurant/Bar, which is located directly South of the
proposed Grand Tower, to allow ingress/egress across the property
line.
Fourth, that in the future, buildings which are constructed on
parcels adjoining the site to the North and South shall comply with
Building Code Requirements for set-back from the property line and
shall not be allowed to utilize the easement as a credit for
compliance with Building Code requirements.
Motion seconded by Mr. Kamm, motion carried unanimously.
In support of this decision the Board make the following findings
of fact:
A public way is normally located outside of a public
property. In this case the easement is located inside
Building Board of Appeals
Minutes
May 9, 1989
Page 4
the applicants property. Consequently, it is the Boards
holding that the distance for protection of openings
shall be measured from the building fact to the property
line and not -to the center of easement.
If the conditions which are recommended by the Board
are integrated into the agreement, it will ensure that
building set-backs in accordance with the Uniform
Building Code will be maintained.
Upon satisfactory completion of the conditions of the
recommended agreement, the Building Board of Appeals
will formally grant the appeal .
It was moved by Mr. Kamm, seconded by Mr. Throop to adjourn.
Motion carried.
Meeting adjourned at 5:12 p.m.
Respectfully submitted,
ack A. Nelson
ecretary
Minutes Approved On:
OFFICIAL PROCEEDINGS
of the
BUILDING BOARD OF APPEALS
February 20, 1990
The regular meeting of the City of Lansing, Building Board of Appeals
was held on Tuesday, February 20, 1990 , at 2:00 p.m. in the Building
Safety Division Conference Room, 119 North Washington Square, Lower
Level , Lansing, Michigan.
The meeting was called to order by Chairman Richard Stuckman at
2:04 p.m. with a roll call showing the following members present:
Members Present:
Richard Stuckman, President
Richard Jones, Vice President
Frank Throop, Member
Randall Kamm, Member
Joe Wilcox, Member
Staff Present:
James W. Kzeski , Director of Building Safety
Jack Nelson, Recording Secretary
Dennis George, Fire Inspector
On a motion by Mr. Jones , supported by Mr. Throop, the minutes of
December 12, 1989, were approved.
The following appeals were addressed by the Board:
Appeal #90-001 : Hawaiian Paradise
The subject of the hearing was the consideration of a request from
Mr. Glenn C. Harr, Vice President, Hawaiian Paradise, Suite #133,
1900 South Cedar Street (old Walter French Junior High) .
Mr. Harr requested authorization to allow the use of the existing
kitchen in the facility for a catering business. Hawaiian Paradise
has occupied the facility for approximately 12 months. The business
is currently licensed by the Michigan Department of Agriculture to
operate a seafood repackaging operation. Fresh fish and seafood is
flown to Michigan and repackaged to deliver to accounts in the
mid-Michigan area. The business also sells tropical flowers, kona
coffee and macadamia nuts.
Ch Z Wd - 6T M 06,
ONISNVI '00211
Building Board of Appeals
Minutes
February 20, 1990
Page 2
Mr. Harr stated that he would like to expand the operation to
include catering . The operation would not include any type of
equipment that would produce excessive heat or produce grease-laden
vapors. A convection oven is currently utilized for baking. Hawaiian
Paradise also prepares fruit and vegetable trays with main course
entrees that are either baked or grilled on-site with charcoal
grills. The only purpose of the exhaust vents to on system would
be to pull heat from the kitchen area.
The Buiding Safety Division presented the following information:
The existing kichen does not comply with current Mechanical and
Building Code requirements as follows:
Kitchen Ventilation System (U.M.C. 1988 Edition, pg. 133)
Section 2002 (a) (b) (c) (d) (f) and (e)
Hood System (U.M.C. 1988 Edition)
2003 (b) (c) (g)
Building Code Violations
Table 5-A, 504(c) , 4306(J)
Chairman Stuckman requested comments from the Fire Prevention Bureau.
Dennis George, Fire Inspector, stated that the Fire Prevention Bureau
had no objection to the variance as along as the corridor which
leads to the exterior court is not used as a means of egress for
the building.
After discussion, Mr. Jones moved, supported by Mr. Wilcox, to
approve this case. The approval is subject to the following condi-
tions.
1. The main corridor within the building which leads to this
tenant space and to the court shall not be used as means of
egress for the building.
2. The variance is only issued to Hawaiian Paradise for their use
only and is not transferable.
3. Tenant shall not use a deep fryer or grill , or any other type
of equipment that would produce excessive heat or grease build-
up in the ventilation system.
4. The tenant shall authorize the Fire Prevention Bureau and the
Building Safety Division to perform unannounced periodic inspec-
tions of the tenant space.
Building Board of Appeals
Minutes
February 20, 1990
Page 3
In support of this decision the Board makes the following findings
of fact:
1. The corridor system which the unprotected duct passes through
will not be utilized as a means of egress for the building.
2. The tenant will not be authorized to use the hood system for
any quipment which produces excessive heat or discharges
grease-laden vapors.
3. The Fire Prevention and Building Safety Divisions will monitor
the facility on a periodic basis to ensure continued compliance.
Appeal r'90-002: Dale Goodrich, Lansing Reinvestment
An Application for variance has been filed by Mr. Dale Goodrich,
209 Church Street, Potterville, Michigan, on behalf of Lansing
Reinvestment. The applicant seeks relief from the enforcing
officer' s field correction notice which required that bedroom egress
windows comply with Section 1204 of the Uniform Building Code.
Mr. Goodrich stated that a Building Permit was acquired on November
30, 1989, for interior remodeling and siding of an existing single
family residence at 228 Hill Street. The value of the alteration
was approximately $10,000.00. All windows in the house were replaced
with a vinyl replacement windows which were installed in the existing
window openings.
On or about January 4, 1990, Mr. Jon Wadsworth, Building Inspector,
conducted an inspection and noted that the bedroom windows did not
comply with Building Code requirements.
Mr. Goodrich also stated that his appeal has been amended to request
a variance for the northwest bedroom only. The windows in the rest
of the bedrooms have been changed. The net clear opening of the
window in question is 29" wide by 23" in height. The code requires
a net clear width of 20" and height of 24" and a clear opening of
at least 5.7 sq. ft. In this case the net opening is 4.63 sq. ft.
Chairman Stuckman requested staff comments:
Dennis George, Fire Inspector, stated that 'the primary reason for
the net clear opening is to afford sufficient clear area for a
fireman to enter the bedroom with equipment. Inspector George
indicated that the window dimension would not prevent a fireman
from entering the building through the window.
Building Board of Appeals
Minutes
February 20, 1990
Page 4
After discussion, Mr. Throop moved, supported by Mr. Jones, to
approve the variance for the window in the northwest bedroom only.
Motion carried unanimously.
In support of this decision, the Board makes the following findings
of fact:
1. The window area and clear height will not, in the Boards opinion,
adversely effect fire fighting rescue.
2. The net clear height requirement is 24" . The appeal request a
variance of only 1" in height and 1. 1 sq. ft. in area. The
Board feels that the variance request is the minimum necessary
to alleviate the situation.
3. The window installed was in the existing opening and no framing
was necessary to accommodate the new window.
Appeal #90-003 : Victor Office Center
An Application for a variance was filed by Mr. Peter Holtz, Architect,
Victor Design, on behalf of Gentilozzi Real Estate and Management
Company, One Michigan Avenue, Suite 200, Lansing, Michigan.
The request, if granted, would allow the use of fusible link devise
to mount window blinds on the west side of the new Victor—Office
Building which is locacted on the Northwest corner of Ottawa and
North Washington Square.
The Building Board of Appeals previsouly addressed a request by
this Applicant on December 13, 1988. The Applicant at that time
requested the use of unrated glazing in the west wall of the Victor
building. Protected openings would have been required due to the
proximity of the building to the property line. The Board granted
the variance, but predicated its approval upon compliance with
several conditions . Condition #3 stated that " . . . curtain rods,
blinds or other window treatments shall not be positioned to adversely
effect the sprinklers which were required to protect the glazing. "
The Applicant now wants to install window blinds on the windows
with the fusible link system. Since this request effects a previous
board action, the Department is requesting disposition by the Board.
Mr. Holtz presented the case to the Board stating that a similar
appeal was granted by the Building Board of Appeals for the City of
East Lansing. Mr. Holtz also stated that the fusible links ar UL
rated to hold up to 20# and release at 135° . In the event of a
fire these links would break the blinds, and in total would drop
away from the window before the sprinklers were actuated. This
system would allow the same degree of protection while allowing
tenants to install window treatment for privacy and cooling from
the afternoon west sun.
Building Board oL Appeals
Minutes
February 20 , 1990
Page 5
Chairman Stuckman requested staff comments:
Inspector Dennis George stated that the sprinkler heads which protect
the glazing are quick response heads which could discharge prior to
the release of the fusible links for the blinds. There is a time
factor delay on the fusible link which does not occur on the
sprinkler. If the blinds did not fall , the windows would not be
cooled by the sprinkler system. This scenario would be critical if
we had an exterior fire exposure from the Ingham Building.
After discussion, Mr. Throop, supported by Mr. Kamm, moved that the
request be denied. Motion carried unanimously.
In support of this decision the Board makes the following findings
of fact:
1. It is imperative that there are no obstructions which will
adversely affect the quick response sprinklers and their ability
to cool and protect the exterior wall glazing on the west side
of the building. The Applicant did not substantiate that the
proposed system would function under fire conditions to the
degree necessary to authorize the variance.
2. The issuance of the variance may substantially deviate from
performance required by the code in relation to fire safety
and protection of the exterior glazing since the blinds may
impede the sprinkler system. "
TABLED APPEALS:
Appeal #89-004: Grand Tower
On May 9, 1989, the Board tabled Appeal #89-004 in order to afford
time to the City of Lansing and Gentilozzi Real Estate to consumate
a written agreement between the parties, concerning the conveyance
of property for the construction of the Grand Tower Office building.
The Board had stated that the variance would be approved if the
following conditions were complied with.
The Board of Appeals recommended that language be drafted as a part
of the agreement between the parties which would define the public
access easement as not adversely effecting the construction of the
Grand Tower building; that is to say for purposes of construction
the City would not treat the easement as a public way.
Second, Gentilozzi Real Estate grant an easement to the Black and
Tan Restaurant/Bar, which is located directly South of the proposed
Grand Tower, to allow ingress/egress across. the property line.
Building Board of Appeals
Minutes
February 20, 1990
Page 6
Third, that in the future, buildings which are constructed on parcels
adjoining the site to the North and South shall comply with Building
Code requirements for set-back from the property line and shall not
be allowed to utilize the easement as a credit for compliance with
Building Code requirements.
At the meeting the final terms of the property settlement were
reviewed and approved on a motion by Mr. Throop, supported by Mr.
Jones. Motion carried unanimously.
Appeal #89-005: Main Street Day Care (Reconsideration Request)
The subject of the hearing was a variance request from the Main
Street Child Care Facility located at 1715 W. Main Street.
The purpose of the request is to seek authority from the Building
Board of Appeals to utilize the second floor of the building for
day care purposes. Section 802(c) of the Uniform Building Code,
1988 Edition, requires that day care shall not be located above the
first story unless the building is totally fire suppressed.
This case was previously denied by the Board in December, 1989.
The Applicant has amended the request and seeks a rehearing on the
case.
The Applicant is proposing to install smoke detectors on the first
floor of the building and install sprinklers in the exit cor"ridors
also on the first floor, and sprinkle the entire second floor.
This proposal deviates from the original proposal in that fire
suppression is now proposed in the first floor exit corridors.
Mr. Russell Hinkle, Architect, Stein, Hinkle, Dawe, Wood and Johnson,
presented the case on behalf of the day care center. Mr. Hinkle
represented that the first floor was remodeled two years ago and
requiring a sprinkler system on the first floor would adversely
effect the existing construction as well as disrupt the operation.
Mr. Hinkle also stated that the second floor would be utilized for
latch key programs , consequently, the children occupying the area
are of sufficient age to negotiate the stairshaft.
Mr. James Kzeski presented the position of the Building Safety
Division. He stated that there are several positive attributes of
the building which may be viewed as equating with the requirement
for total fire suppression. Those items which exceed minimum code
requirements are as follows:
Building Board of Appeals
Minutes
February 20, 1990
Page 7
A smoke detection system would be installed in the entire building.
The building exceeds the minimum construction type. A rated fire
separation will be provided between the floors. The second floor
is provided with three independent exits and the second floor will
be utilized for latch key children only (2nd, 3rd, and 4th graders) .
Dennis George, Fire Inspector, voiced his objection to the proposal
indicating that fire suppression requirements cannot be traded for
other code items.
After discussion Mr. Throop moved, supported by Mr. Jones , that the
variance be approved as requested. Motion carried unanimously.
The variance is subject to compliance with the following conditions:
1. The entire second floor, all corridors and stairshafts shall
be equipped with a fire suppression system installed in
compliance with N.F.P.A. requirements. The system shall be
installed by a licensed sprinkler installer. Plan shall be
approved by the Fire Prevention Bureau.
2. The mechanical shafts which are utilized as an air plenum
shall be sealed at the floor system with an assembly which
will afford a one-hour fire-resistant barrier.
3. Only latch key children will be authorized to occupy the-second
floor, e.g. 2nd, 3rd, 4th grade or older.
This decision is based upon the following findings of fact:
1. All class rooms on the first floor, except one, has direct
exiting to the outside. Second, the second floor has three
stairshafts which exit directly to the exterior of the building.
These attributes will ensure safe and expeditious exiting from
the building.
2. The construction of the building exceeds the minimum construc-
tion type. The increase in fire resistance will equate favorably
with the lack of fire suppression on the first floor class
rooms.
3. The variance approval will limit the age of children on the
second floor to those capable of exiting the building without
continued supervision.
OTHER BUSINESS:
The Board was requested to review proposed changes in the fee schedule
for the Building Safety Division.
Building Board of Appeals
Minutes
February 20, 1990
Page 8
After discussion, Mr. Jones moved to approve the proposed changes
in the fee schedule. Motion supported by Mr. Throop. Motion
carried unanimously.
It was moved by Randall Kamm, supported by Mr. Wilcox to adjourn.
Motion carried unanimously.
Meeting adourned at 4:18 p.m.
Respectfully submitted,
eording
lson
Secretary
Minutes approved on
OFFICIAL pROCEEDINGS
Of the
DING BOARD OF APPEALS
gUl 199D guildin9 Appeals
April 10,
Board of
Safety pivision
Mich an.
of the City °f Canln the BuildLansing, lg
1990ton uare, at
meeting ril 10, Sq Stuckman
The held on Tuesday119p N. Washing Ria d tituted a
was Room Chairmancons
Conference order by resent
alled to Were P
ting T
he me he f 11 Wing members
T
2_p5 p'm•
quorum
T ` nt
ers PreSe Stuckman, Preside dent
Memb Ares
RAchard Bones , Vice
915
Richard hroop, Member
o— Frank Kamm, Member
3oedaAA Wilcox, Member
Staff present: Fire Recording Secretary by Mr•
d O t piBrien, motion
y� Gary Brydges, Acting the agendas °OnFebrua rare 1990,
ti on °f the mi nut had been no
ere Was no modlbycMr• Jonas, at there
Th Supportedlt Was note
th
Thro°P,approved. by the Board:
Were ameeting.
Board appeals Were addressed
The following Side Deli the tenant, thets,de
1g$g
p-004: West ented a of its
APPeaI #9 resent andal ng eSecti0W0uld requAr Washington
apP Code which at 22p S. space used
Gordon FTheo aPPlaca P m guildin9 located feet of P the
De
IA -. On' Structure 000 square ant Spaces °tenant
Edition of the
om the ba5emn Ludes pprOX�mateltw°� SeParate tfhe adjacent
fr t and being Westside Dell
The basf or Storage, them He Stated
mostly of matter d the
t floor, one the
building, an
firs formation on Barr
is Barry, s place• new inform er and that
ut presente e some ey Ros abo t to eXPit e, a new a air ce
S1 Was tune At that. tine, Barry• pia
° be
Mr• t the lease twee place is ow
tropr1etor °fbeavacatin9hebasement into
s c Wha
p basement
would likely be d from
Would be
Building Boai of Appeals
Minutes
4/10/90
Page 2
Mr. Fineout was not able to say at this time when the space would
be vacated, nor when the .stairs would be erected. Mr. Fineout said
he would provide a letter to the Building Safety Division expressing
a definite time of installation for the new stairs.
Mr. Stuckman suggested that since the Applicant was now willing to
install the second stairway, there was no need for an appeal .
However, there was the question of when the stairs would be done.
A motion was made by Mr. Throop, supported by Mr. Wilcox that the
appeal be tabled until the next meeting. This would allow approx-
imately 30 days to get a letter to the Building Safety Division.
Occupancy of the first floor and basement could continue during
that period. If the need for an appeal was still evident at the
next meeting it could be acted upon at that time; otherwise the
appeal would be withdrawn. Motion carried unanimously.
Appeal #90-005: 462 E. Edgewood, Retail "B"
Mr. Michael Meldrun, MMA Associates, was present and represented
RAMCO - Lansing Associates. The appeal related to the termination
of an area separation wall with an adjacent canopy overhang. The
requirement for the two-hour area separation wall was the result of
an agreement between the separate owner/developers of the Edgewood
Center complex.
Mr. Meldrum explained the situation and the basis for the appeal .
He stated that the store front would lose nearly half of its glass
exposure if required to comply with Section 505(e) of the Uniform
Building Code, 1988 Edition. This would lessen the desirability of
the space and make it difficult to lease. Mr. Meldrum stated that
polished wire glass , which would be an acceptable alternative to a
solid wall , would take from four to six months to get and is very
expensive.
Discussion of the matter centered on whether there was actually a
need for the appeal . It appeared that Section 505(e) (2) of the
Code was being complied with as shown on the drawings , and that the
requirements in the Exception under Section 505(e) (2) should not
have been invoked. The reasoning for this was that the area separa-
tion wall extended beyond the outer edge of the canopy projection.
The Exception would only be applied where an area separation wall
terminated at the intersection of an exterior wall with a canopy
projecting beyond that point.
Since it was unclear as to why this part of Section 505 was called
out during the plan review process , it was suggested that Mr. O'Brien
and Mr. Brydges discuss the matter with Jack Nelson upon his return
from vacation.
Building Boara of Appeals
Minutes
4/10/90
Page 3
It was moved by Mr. Jones, supported by Mr. Throop, that the appeal
be tabled for one week following the forthcoming dicussion with Mr.
Nelson. If there is indeed no need for an appeal , it will be
,automatically withdrawn. If, in fact, the appeal is required, a
special meeting will be set for the Board on Tuesday, April 17,
1990, to hear the matter again. Motion carried unanimously.
There being no other business before the Board, and no public comment,
Mr. Throop moved the meeting be adjourned, supported by Mr. Wilcox.
Meeting adourned at 3:15 p.m.
Respectfully submitted,
c
Gary rydges,
Acting Recording Secretary
Mintues approved on
OFFICIAL PROCEEDINGS
of the
BUILDING BOARD OF APPEALS
May 8, 1990
The regular meeting of the City of Lansing, Building Board of Appeals
was held on Tuesday, May 8, 1990, in the Building Safety Conference
Room, 119 N. Washington Square, Lansing, Michigan.
The meeting was called to order by Chairman Richard Stuckman at
2:03 p.m. The following members were present and constituted a
quorum:
Members Present:
Richard Stuckman, President
Richard Jones , Vice-President
Frank Throop, Member
Randall Kamm, Member
Members Absent:
Joe Wilcox, .Member
Staff Present:
Jack Nelson, Recording Secretary
Robert O'Brien, Fire Marshal
Randy Eberbach, Code Compliance Officer
There were no modifications to the agenda. On a motion by Mr.
Jones , supported by Mr. Throop, the minutes of the April 10, 1990,
were approved as printed.
The following cases were addressed by the Board. Chairman Stuckman
explained the rules of procedure to the first applicant.
OLD BUSINESS:
Appeal #90-004: Westside Deli , 220 S. Washington
This appeal was tabled at the April 10, 1990, meeting in order to
afford the applicant time to acquire a letter from the building's
owner which delineates a timetable for the installation of the
stairway. It was the Boards opinion that if the stairway was
installed with dispatach, the -appeal could be withdrawn.
On April 30, 1990, the Department received a letter from the
building 's owner. The letter , stated that the lease for Barry's
Tz
ONISNV7
Building Board of Appeals
Minutes
May 8, 1990
Page 2
Place would not expire until October 31, 1991. Second, it was
stated that he wanted to proceed with the variance request and not
install the second stairshaft. Mr. Rosenberg cited the fact that
total remodeling of 220 S. Washington was only 25% of the square
footage of the entire building. The basement is currently sprinkled
and has hard wired smoke detectors.
Mr. Mark Fineout was present and represented the owner, Mr. Sidney
Rosenberg. The applicant is appealing Section 3303(a) of the 1988
Edition of the Uniform Building Code which requires two exits from
basement areas which are utilized for storage and exceeds 300 square
feet. The basement is approximatley 7,000 square feet and is utilized
for storage. The storage area underlies two separate tenant spaces
on the first floor; one being Westside Deli . The adjacent tenant
is Barry's Place. Mr. Fineout stated that the owner is requesting
a variance from installing the stairway.
Chairman Stuckman asked for the .position of the Fire Prevention
Bureau. Robert O'Brien stated that the size of the basement, coupled
with its use, would necessitate two exits.
The Board had general discussion concerning the case.
Mr. Throop moved to deny the appeal , motion supported by Mr. Jones.
Motion carried unanimously.
In support of this decision the Board makes the following findings
of fact:
1. The area of the basement poses a potential hazard to occupants
which utilize the area for storage. The distance from remote
areas of the basement to the one stairshaft could adversely
affect safety exiting under fire conditions.
It is the Boards decision to require that the second exit be installed
within 60 days from the date of this meeting.
NEW BUSINESS:
Appeal #90-006: Rodney Smith, 2035 Moffitt
An Application for variance has been filed by Mr. Rodney Smith for
his residence. The request, if granted, would allow the use of a
bedroom and sitting room in the basement of his residence with a
ceiling height of 7 '0".
Section 1207(a) , Ceiling Heights, of the 1988 U.B.C. , states that
habitable space shall have a ceiling height of not less than 7'6".
Building Boar , of Appeals
Minutes
May 8, 1990
Page 3
Mr. Smith was not in attendance at the meeting. However, the Board
felt that the case could be addressed without the applicants presence.
According to the Departments records, the violation was noted by
Mr. Robert Graham, Building Inspector, while performing an inspection
of a garage on the same site. The applicant represented to Mr.
Graham that he was not aware that a permit was required for the
alteration.
After discussion it was moved by Mr. Jones, supported by Mr. Kamm
that the request be approved. Motion carried unanimously.
In support of this decision, the Board makes the following findings
of fact.
1. The ceiling height exception does not adversely affect the
health, safety and welfare of the occupants.
2. As a condition for approval , smoke detection will be required
in accordance with Chapter 12 of the U.B.C. 1988 Edition.
Appeal #90-007: Hall-Springtree Associates, 3029 Beau Jardin Dr.
An Application for appeal was filed by Mr. Scott Kenney on behalf
of Hall=Springtree Association, 3029 Beau Jardin Dr. , Lansing,
Michigan.
The application, if approved, would allow the continued use of
guardrails on exterior balconies at Springtree Apartments which are
30" in height. Second, the management takes exception to the instal-
lation of handrails on the primary entrance stairways.
On or about November 15, 1989, Randall Eberbach, Code Compliance
Officer, issued a Correction Notice for several buildings at the
Springtree Complex which is located on Beau Jardin Dr. The violation
notice was issued pursuant to the requirements of Section
1460.20(2) (J) of the Title Six Housing Code, City of Lansing. Mr.
Eberbach declared the buildings to be substandard since no handrails
were provided on the primary entrance stairways and since the guard-
rails on the exterior balconies are 30" in height.
The applicant contends that the buildings were constructed between
1968 and 1971. At the time of construction, and the issuance of
the Occupancy Permit, there were no handrails leading to the entrance
of the building. The entrances have not been altered since construc-
tion and the property has been subject to annual inspections through-
out its history. At no time was the complex cited for lack of
handrails.
Building Board of Appeals
Minutes
May 8, 1990
Page 4
Second, in 1987, the applicant began an extensive plan to repair
all balconies at the request of the Building Safety Division. The
work involved replacement of rotted structural members, replacement
of rotted decking and addition of vertical supports as necessary.
It is the applicants position that several thousand dollars has
been expended to repair the balconies under the supervision of the
Building Safety Division, and at no time did the Building Inspector
require alteration to the guardrail .
According to the Department's file, the building permits issued to
Springtree Apartments were for repair work per the requirements of
Section 104(d) of the Building Code (U.B.C. 1988 Edition) . Since
the work was only repair and maintenance, the Building Inspector
did not require the replacement of the existing iron railing.
Randy Eberbach, Code Compliance Officer for the City of Lansing,
Building Safety Division, explained the City's rental inspection
program. Mr. Eberbach stated that the program requires that all
rental dwellings be inspected on a two year cycle.
Scott Kenney, Springtree Apartments Representative, stated that
management has spent thousands of dollars to improve the safety as
well as the esthetics of the balconies under the supervision of the
Lansing -Building Safety Division. He did not feel that 'it is
justifiable to spend additional money to install new guardrails on
the balconies, and handrails on the entry stairways.
Chairman Stuckman stated that a condition exists that allows a
potential hazard that must be corrected. It is, however, unfortunate
that enforcement did not occur earlier.
After general discussion, it was moved by Mr. Jones, supported by
Mr. Throop to deny the appeal . The guardrails on the decks and the
handrail at the primary entrances shall be installed in accordance
with the following schedule:
Handrails and guardrails shall be installed in accordance with the
requirements of the U.B.C. 1988 Edition for the following buildings
in the year indicated.
1990
1. 2900 Beau Jardin 3. 2814 Beau Jardin
2. 2910 Beau Jardin 4. 2800 Beau Jardin
1991
1. 4904 Bell Chase 4. 2911 E. Jolly
2. 4924 Bell Chase 5. 4905 Dunckle
3. 2901 E. Jolly 6. 4925 Dunkle
Building Boars ,f Appeals
Minutes
May 8, 1990
Page 5
1992 (By July 1)
1. 3101 Beau Jardin
2. 3021 Beau Jardin
3. 3027 Beau Jardin
Motion carried unanimously.
In support of this decision, the Board makes the following findings
of fact:
I . According to the record, the housing units in questions were
constructed between 1968 and 1971. The buildings were
apparently constructed under the requirements of the 1967
Building Code. Section 1714 of the code states that guardrails
shall be not less than 36" in height. A review of the 1964
and 1970 Codes also represent that guardrail heights were
consistent with the 1965 Code and at no time were 30" rails
authorized around decks or porches.
2. A code review of the requirements for exterior handrails was
also researched. It was determined that handrails were a code
requirement at the time the units were constructed.
3. A potentially hazardous situation exsists on the site which
must be corrected even though it appears that the violation
was not cited by the City of Lansing, Building Safety Division.
There being no other business before the Board, and no public comment.
Mr. Jones moved the meeting be adjourned, supported by Mr. Kamm.
Motion carried. Meeting adjourned at 3:07 p.m.
Respectfully sub itte ,
ck A. Nelson
S cretary
Minutes Approved On: